KM-1 Medium-Voltage Switchgear 6(10) kV
KM-1 series switchgear is a line of complete medium-voltage panels designed for the reception, distribution, and switching of three-phase power at 6 and 10 kV, 50/60 Hz. Cubicles are intended for operation in systems with an isolated neutral as well as in systems where the neutral is grounded through an arc-suppression coil (Petersen coil) or an active resistor (as per project documentation).
The KM-1 base platform is a modular sheet-steel enclosure of increased rigidity with front doors and rear removable panels, divided into functional compartments by solid metallic/insulating partitions. This sectioning ensures mechanical strength, electrical and fire safety, and simplifies maintenance. The design supports both withdrawable (draw-out truck) and fixed-mounted implementations.
Scope of use
- Substations of utilities (6-10 kV MV rooms, distribution points, main step-down substations) and auxiliary systems of power plants;
- Power systems of industrial facilities (oil & gas, mining & metals, chemicals, machinery);
- Power supply for agricultural sites and municipal infrastructure;
- Retrofit of existing indoor MV rooms with bus and cable routing interfaces preserved.
Service conditions
- Indoor installation up to 1000 m altitude;
- Environmental classification - EN/IEC 60721-3-3 (stationary, weather-protected locations);
- Temperature and humidity ranges - per project specification and installation category;
- Non-hazardous atmosphere, free of conductive dust and aggressive vapors/gases.
Design features
- Rigid modular steel framework with corrosion protection (painted and galvanic finishes);
- Functional compartmentalization: withdrawable breaker, cable, busbar, relay/control;
- Bottom MV-cable entry via cable trenches; terminations in the cable compartment;
- Connection of up to 4 MV cables of 3x240 mm² (as per project);
- Feeder interfaces via both cable and busbar incoming/outgoing connections;
- Unified core assemblies and sizes regardless of main-circuit schemes.
Configuration and variants
- With withdrawable unit: vacuum circuit-breaker, voltage transformers, station/control-power transformer (CPT), earthing switch, etc.;
- Without withdrawable unit: solid-incoming panels, cable transition/termination panels, bus sections;
- Relay compartment: protection & control IEDs, metering/accounting, SCADA interfaces, terminal blocks, DC auxiliary supply;
- Busbars and bus system - copper/aluminium; sectionalizing per project.
Compliance with standards
- IEC 62271-1, IEC 62271-200 (metal-enclosed MV switchgear up to 52 kV);
- IEC 62271-100 (circuit-breakers), IEC 62271-102 (earthing switches);
- IEC 61869-2/-3 (current and voltage transformers);
- EN/IEC 60529 (degrees of protection, IP);
- EN/IEC 60721-3-3 (environmental conditions - indoor, weather-protected);
- EN/IEC 61000-6-2 (EMC immunity, industrial) / EN/IEC 61000-6-4 (EMC emissions, industrial).
Technical data
| Rated voltage, kV | 6; 10 |
| Highest system voltage, kV | 7.2; 12 |
| Rated current of main circuits, A | 630; 1250; 1600; 2000; 2500; 3150 |
| Rated busbar current, A | 1250; 1600; 2500; 3150 |
| Short-time withstand current (3 s), kA | 20; 25; 31.5 |
| Peak (dynamic) withstand current (1 s), kA | 51; 64; 81 |
| Maintenance access | two-sided |
| Insulation level per IEC 60071-1:2019 | standard |
| Environmental conditions | EN/IEC 60721-3-3 |
| Degree of protection | IP31 (EN/IEC 60529) |
| Overall dimensions, mm - width - depth - height |
750; 900; 1100 1300 2150 |
We offer documentation for manufacturing KM-1 switchgear:
- Pre-tender documentation: single-line diagrams, inquiry sheets, and technical description;
- Working drawings, 3-D models, BOM, secondary schematics, and cable schedules tailored to your production;
- Arranging contract manufacturing of enclosures/assemblies with partners; you perform assembly, installation, and routine factory tests;
- Adapting the package to project requirements and your plant's manufacturing capabilities;
- Transition/interface panels for integration with third-party equipment and existing MV rooms.
Why work with us:
- No need to expand engineering staff: the documentation set targets engineers of average qualification;
- Series launch without pilot prototypes thanks to unified assemblies and proven solutions;
- Expert support on assembly, commissioning, and integration of protection/SCADA, plus guidance on KM-1 manufacturing nuances.
For additional information on KM-1 switchgear contact: inbox@proekt-energo.com
...as is well known, an error at the design stage leads to tenfold costs in manufacturing and hundredfold in operation. Timely engineering mitigates budget impact and reduces downtime risks.