K-26 (K-XXVI) Medium-Voltage Switchgear 6(10) kV
KRU K-26 (K-XXVI) is a line of medium-voltage cubicles for receiving and distributing three-phase power at 6/10 kV and 50/60 Hz in systems with an isolated neutral or with a neutral grounded through an arc-suppression reactor/active resistor. The series is intended for indoor switchrooms with regular switching operations using vacuum circuit-breakers.
The base design is a rigid welded steel enclosure with a powder-coat finish. The internal volume is divided by solid metallic and glass-epoxy barriers, plus automatic shutters, providing compartmentalized fault containment and safe maintenance. Lineups are assembled from standardized bays with unified primary and auxiliary modules.
Applications
K-26 is used in indoor substations and plant power systems:
- System and shop substations 6-10 kV, distribution points and package substations;
- Energy complexes of industrial sites, oil & gas and mining sectors;
- Utilities and process infrastructure (pumping stations, data centers, water utilities, etc.);
- Retrofits of existing switchgear and integration with installed feeders and cable routes.
Service conditions
- Indoor installation; altitude up to 1000 m (above this - apply insulation/cooling recalculation);
- Temperature range: -25...+40 °C (for sub-zero operation, heat the switchroom);
- Non-hazardous area, free from conductive dust and aggressive vapors/gases; environmental conditions per EN/IEC 60721-3-3;
- Service access - single- or double-sided (per substation design).
Design features
- Compartmentalization: protection/LV compartment · withdrawable unit (truck) compartment · busbar compartment · cable compartment;
- Shutter mechanism that automatically closes fixed contacts when the truck is moved to the test position;
- Configurations: with trucks; without trucks; mixed (part of equipment fixed, part on the truck);
- On the truck: vacuum CBs, VTs, station-service transformers up to 5 kVA, HRC fuses for remote SST protection;
- Busbars and links in copper/aluminium; sectioning and buswork per project;
- Top/bottom cable entries; interlocks and directed pressure relief are provided.
Scope of supply and variants
- CB bay (with truck): enclosure, withdrawable unit, busbars, protection/LV compartment;
- Bays without truck: solid busbar inlets, cable assemblies/terminations;
- Mixed layout: VT on a truck, part of equipment fixed in place;
- Components: circuit-breakers, disconnectors, earthing switches, post/bushing insulators - 10 kV; VTs, surge arresters, HRC fuses, station-service transformers - 6 or 10 kV (as specified).
Standards compliance
- IEC 62271-1 - common specifications for MV switchgear and controlgear;
- IEC 62271-200 - AC metal-enclosed switchgear up to and including 52 kV;
- IEC 62271-100 - AC circuit-breakers; IEC 62271-102 - disconnectors and earthing switches; IEC 62271-103 - switches;
- IEC 61869-2/-3 - instrument transformers (CTs/VTs); IEC 60529 - degrees of protection (IP code);
- IEC 61000-6-2/-6-4 - EMC (industrial immunity/emissions).
Reliability and lifetime
- Compartmental arc containment with directed pressure relief - adjacent bays remain serviceable;
- Mechanical/electrical interlocks prevent hazardous operations; shutters can be padlocked;
- Rigid metal structure minimizes vibration effects from truck movement and switching;
- Corrosion resistance: galvanized steel and powder-coated facades for long-term service.
Technical data
| Rated voltage, kV | 6; 10 |
| Highest system voltage, kV | 7.2; 12 |
| Rated frequency, Hz | 50; 60 |
| Rated current of main circuits, A | 630; 1250; 1600; 2000; 2500; 3150 |
| Rated busbar current, A | 1250; 1600; 2500; 3150 |
| Rated short-circuit breaking current (CB), kA | 20; 25; 31.5 (per project) |
| Short-time withstand current (3 s), kA | 20; 25; 31.5 |
| Peak (dynamic) withstand current, kA | 51; 64; 81 |
| Power-frequency withstand (1 min), kV | 28; 42 (for 7.2/12 kV classes) |
| Lightning impulse withstand (LI), kV | 60; 75 (typical) |
| Busbar material/system | copper / aluminium; sectioning per project |
| Cable entries | top; bottom (per spec) |
| Cable terminations | up to 3×3-core ≤240 mm² or up to 6×1-core ≤630 mm² |
| Service access | single-sided; double-sided |
| CB endurance class | M2 / E2 / C2 (per project) |
| Internal arc classification (IAC) | AFL / AFLR (parameters per spec) |
| Environmental classification / location | EN/IEC 60721-3-3 |
| Degree of protection (IEC 60529) | IP31 (higher ratings on request) |
| Overall dimensions, mm - width - depth - height |
900; 1100 1660 2370 |
We offer documentation for manufacturing KRU K-26:
Tender package. Single-line diagrams, questionnaires, and technical descriptions for procurement and feasibility assessment.
Working drawings and 3-D models. Layout/assembly drawings, BOM, secondary schematics, cable schedules - tailored to your production.
Contract manufacturing of assemblies. We arrange fabrication of enclosures and mechanisms with certified partners; you perform assembly, installation, and factory tests.
Adaptation and integration. Equivalent/transition bays for interfacing with existing busbars/secondary circuits and third-party equipment.
Benefits of working with us:
No extra staff. Documentation is optimized for supervision by a mid-level engineer.
Fast series launch. Standardized modules and typical solutions reduce schedule and risks.
Technical support. Consulting on assembly, commissioning, and digital integration of protection/SCADA.