Working design documentation for the manufacture of electrical equipment for substations. 3D models. Drawings. Regulatory documentation.

KVE-10/13 Switchgear - Withdrawable Element Replacement (Retrofit)

The KVE-10/13 retrofit is not a “box-for-box” swap. It is an engineered re-configuration of the medium-voltage switching unit that preserves the existing cubicle and terminations. We design and supply a withdrawable truck that mirrors the KVE-10/13 mating geometry, integrates a modern vacuum circuit breaker (VCB), and extends functionality without full switchgear replacement. The goal is long-term reliability, reduced operational risk, and readiness for digital operation scenarios.

What the KVE-10/13 retrofit solves

  • Service life & predictability: a vacuum interrupter delivers stable switching performance and long mechanical endurance.
  • Robust interlocking: prevention of human error, position/status control of all critical mechanisms.
  • Ready for P&C/SCADA: unified secondary interfaces, remote monitoring, operation logging.
  • Minimal civil works: the cubicle, busbar systems, cable terminations, and foundation remain in place.
  • No oil handling: eliminates dielectric oil operations, leaks, and related downtime.

Project scope options

We tailor the delivery to your operating scenario and outage windows:

  1. Base-Adapt — install a VCB on the existing truck using adapter frames, tune the shutter assembly, and unify the secondary plug-in cassette.
  2. Drop-in Cart — a new withdrawable truck “to KVE-10/13 form-fit” with mirrored connection dimensions, stops, and interlock logic.
  3. Factory Block — a factory-built module with implemented mechanical/electrical interlocks and shutters, extended FAT program, and door-closed operation capability (per design).

Implementation stages

  1. Engineering survey: field measurements, photo record, review of the single-line and short-circuit data, verification of the secondary scheme.
  2. Design: 3D model of the truck, racking kinematics, force calculation for primary contact engagement, interlock matrix.
  3. Manufacture: frame and adapters, subassembly build, secondary harness marking, mechanism setting.
  4. FAT (factory test bay): verification of “service/test/disconnected” positions, breaker functional operations, secondary continuity checks, test reports.
  5. Delivery & site supervision: on-site geometric verification, SAT, operators’ training.
  6. Energization: final checks, handover of O&M documentation, commissioning to service.

Technical data (typical ranges for KVE-10/13)

ParameterValue / rangeNotes
Rated voltage class, kV 10 (6 on request) Insulation coordination and clearances
Frequency, Hz 50/60 Compatible with modern protection relays
Breaker rated current, A 630–1250 (option 1600) Thermal and dynamic verification
Rated short-circuit breaking capacity, kA 20–31.5 Selection per short-circuit calculations
Mechanical endurance ≥ 10 000 operations Depending on VCB series
Truck positions Service / Test / Disconnected Position latches and indication
Breaker operating mechanism Spring-charged / electro-magnetic Per switching duty profile
Front degree of protection IP per project (typ. IP20…IP54) Improved with covers and gaskets (IEC 60529)
Secondary circuits Removable cassette/connector Unified marking and pinout
Form-fit to KVE-10/13 envelope Yes, “drop-in” Adapter frames and guides included
Testing FAT/SAT + routine tests Reports and checklists

Interfaces and mating tolerances

InterfaceScopeProject control
Primary contacts Plug-and-socket concentricity, closing forces, pole centerline height Templates, gauges, geometry record
Shutter mechanism Auto-closing of apertures when leaving service position Functional runs and position checks
Interlocks Mechanical/electrical; blocking of hazardous actions Interlock matrix and bench scenarios
Secondary connector Keyed cassette, unified X1/X2 pinout Continuity test, labeling, wiring diagrams
Earthing switch Independent drive, indication and interlocking “On/Off” functions and interlocks
Door & IP Front with viewing window, higher IP, anti-condensation measures Seal and ventilation inspection

Options and extensions

  • Door-closed racking — subject to cubicle design.
  • Motorized racking and remote truck position monitoring.
  • Status sensors (O-C counter, coil currents, travel time, drive diagnostics).
  • Compatibility with existing CTs/VTs; VPIS (voltage presence indicating system) installation per IEC 61243-5.
  • Integration with Protection & Control and SCADA/DCS: signal lists, event records, and disturbance archives.

Implementation scenarios — comparison

CriterionBase-AdaptDrop-in CartFactory Block
Project duration Moderate Short Minimal
Factory completeness Partial High Maximum
On-site works Elevated Low Minimal
Sensitivity to geometry High Medium Low/medium
Budget level Low Medium High
Ability to keep old truck as spare Limited Yes Yes

Quality control and tests

  • Geometry and coupling force checks; primary contact alignment control.
  • Interlock and shutter functional scenarios; blocking of unsafe operations.
  • Insulation tests and primary contact resistance measurements.
  • Breaker no-load operation runs, drive and auxiliary circuit checks.
  • Documentation: routine tests per IEC 62271, FAT/SAT reports, inspection sheets, non-conformity and corrective action logs.

Documentation & manufacturing package

Questionnaires, preliminary docs for tenders, complete fabrication drawings (DWG/DXF), 3D models (STEP/Parasolid), BOMs and QA plans, schematic and wiring diagrams, routings, assembly/adjustment guides, routine test procedures, typical retrofit design sets, O&M manuals. Documentation is adapted to your standards and processes.

Service conditions

Indoor MV switchgear rooms with climatic category per project; temperature and humidity per substation conditions; installation altitude up to 1000 m (higher on request with insulation re-assessment); enclosure degree of protection — per specification. On request: anti-condensation measures, reinforced fixings, seismic assessment, and higher IP.

FAQ — KVE-10/13 retrofit

Standards & compliance

The project is executed in line with current medium-voltage equipment and enclosure standards, interlocking requirements, IP ratings, and test programs. On request we configure to modern reliability classes and internal arc classification — evidence by component manufacturers’ documentation and test results (e.g., IEC 62271-200 IAC, IEC 62271-100, IEC 62271-102, IEC 60529).

What you receive

  • Fabrication drawings and 3D models for manufacturing and service support.
  • A drop-in KVE-10/13 truck or an adaptation kit.
  • Test programs and procedures, commissioning checklists, FAT/SAT protocols.
  • P&C recommendations, I/O list for SCADA/DCS, maintenance instructions.

Request documents and pricing: inbox@proekt-energo.com

PDF — Download KVE-10/13 Retrofit Tech Pack

Download PDF: KVE-10/13 truck retrofit

  • Equipment drawings

    Equipment drawings

  • Equipment drawings

    Equipment drawings

  • Regulatory and technical documentation

    Regulatory and technical documentation

  • 3-D models

    3-D models

  • 3-D models

    3-D models

  • Technical specifications

    Technical specifications

  • Operating manual for equipment

    Operating manual for equipment

  • 3-D models

    3-D models

  • Regulatory and technical documentation

    Regulatory and technical documentation

  • Operating manual for equipment

    Operating manual for equipment

  • Operating manual for equipment

    Operating manual for equipment

  • Regulatory and technical documentation

    Regulatory and technical documentation

  • Technical specifications

    Technical specifications

  • Equipment drawings

    Equipment drawings

  • Technical specifications

    Technical specifications

Demo

FEEDBACK FORM