KRU “Omega” Medium-Voltage Switchgear 6(10) kV
The “Omega” series of 6/10 kV medium-voltage switchgear is designed for receiving, distributing, and switching three-phase AC at 50/60 Hz in systems with an isolated neutral or a neutral earthed via an arc-suppression reactor / resistor. The solution targets indoor distribution switchgear of substations and industrial facilities where safety, modularity, and ease of maintenance are required.
The enclosure is a modular steel construction made of galvanized sheet with powder-coated front parts (high corrosion resistance). A distinctive layout feature is the busbar system in the upper rear section, a withdrawable unit in the middle, and the cable/bus compartments beneath it or beneath the busbar compartment. This architecture increases usable feeder volume and ensures full front access, enabling one-sided operation and maintenance when required.
For arc-fault safety the design uses metal-clad compartmentalization with solid metallic and insulating barriers. Typical compartments include: a relay/low-voltage compartment, a withdrawable circuit-breaker compartment, a busbar compartment, and a cable compartment. On request, the truck can be motorized for remote test ↔ in-service movement, and the earthing switch can be equipped with an electric actuator (ON/OFF). Optional features include video surveillance (breaker / earthing-switch compartments) with display at the control desk, contact-temperature monitoring, and a front mimic panel.
Scope of application
“Omega” switchgear is used at generation, transmission, and distribution facilities as well as by industrial consumers:
- Indoor MV switchgear of package substations (KTP) and urban 6-10 kV distribution points;
- Industrial plant substations; auxiliary switchgear of power plants (TPP/HPP/CCPP);
- Utilities and infrastructure: water utilities, pump stations, heat centers, data centers;
- Factory-built modular substations and retrofit of existing switchgear line-ups;
- Back-to-back (double-row) line-ups - interconnection by bus bridges or cables (on request).
Service conditions
- Environmental conditions - EN/IEC 60721-3-3 (indoor); operating ambient -25…+40 °C;
- Altitude - up to 1000 m a.s.l. (above this - insulation/thermal verification by calculation);
- Non-hazardous atmosphere, free of conductive dust and aggressive vapors/gases;
- Degree of protection - IP31 (IEC 60529);
- Maintenance access - one-sided or two-sided, depending on the switchgear layout.
Design features
- Full compartmentalization: LV/relay compartment ⋅ withdrawable unit ⋅ busbar ⋅ cable compartment;
- Withdrawable vacuum circuit-breaker with optional motorized racking (test/in-service);
- Motor drive for the earthing switch (ON/OFF), interlocks per safety logic;
- Options: cameras in breaker/earthing-switch compartments, contact-temperature monitoring, front mimic panel;
- Bus bridges / cable interconnections for double-row line-ups; common earthing bar per IEC 61936-1;
- Multi-point door latching, keyed locks; directed pressure-relief upwards.
Standards compliance
- IEC 62271-200 - metal-enclosed / metal-clad MV switchgear, LSC/PM; internal-arc classification IAC (as specified);
- IEC 62271-100 - 12 kV vacuum circuit-breakers; IEC 62271-102 - earthing switches;
- IEC 60071-1:2019 - insulation coordination (standard insulation level);
- EN/IEC 60721-3-3 - environmental conditions (indoor); IEC 60529 - IP degrees of protection;
- IEC 61000-6-2 / 61000-6-4 - EMC (industrial immunity/emissions).
Reliability and lifetime
- Internal-arc effects confined to a single compartment, minimizing impact on adjacent panels;
- Mechanical and electrical interlocks - prevention of incorrect operations;
- Metal cable ducts for secondary circuits - EMC robustness and serviceability;
- Powder-coated galvanized steel - high corrosion resistance and durability.
Technical data
| Rated voltage, kV | 6; 10 |
| Maximum system voltage, kV | 7.2; 12 |
| Rated current of main circuits, A | 630; 1250; 1600; 2000; 2500; 3150 |
| Rated busbar current, A | 1250; 1600; 2500; 3150 |
| Thermal withstand current (3 s), kA | 20; 25; 31.5 |
| Dynamic withstand current (1 s), kA | 51; 64; 81 |
| Maintenance access | one-sided; two-sided |
| Insulation level (IEC 60071-1:2019) | standard |
| Environmental conditions | EN/IEC 60721-3-3 (indoor) |
| Degree of protection | IP31 (IEC 60529) |
| Overall dimensions, mm - width - depth - height |
650; 800; 1000 1500; 1900 2360 |
We offer documentation for manufacturing KRU “Omega”:
Tender package. Single-line diagrams, data sheets, and technical description for bids and feasibility assessment.
Manufacturing drawings and 3-D models. Layouts, BOMs, secondary schematics, cable schedules.
Contract manufacturing of subassemblies. We place assemblies and parts with partner shops under quality control.
Adaptation to existing equipment. We design drop-in panels to interface with legacy busbars.
Why work with us
No staff expansion. Documentation is clear to a mid-level engineer.
No prototypes required. Proven modules and standard solutions shorten lead time.
24/7 support. Consulting on assembly, commissioning, and digital integration.